Key Features:
1.SORO Outdoor Intelligent High Frequency Online UPS provide continuous pure sine wave AC power supply for
outside communications / network equipment.
2.Double-conversion online design, high temperature resistant, anti-cold, sealing level for IP55; With the wide range of input voltage and frequency of input window (- 45% +35% rated voltage and ± 10% rated frequency), in many remote areas of China after a severe test of the grid.
Application:
This UPS is commonly used in the corner of the city, remote roads, mountains, bad environment, such as high temperature (+50 °C) / low temperature (-40 °C), severe dust, moisture, rain, mist erosion, very poor power quality (voltage longterm higher than 260V or less than 160V, frequency abnormal change) in the area.
High Reliability of the UPS System
1.Using microprocessor control, directly produce highfrequency pulse width modulation wave (SPWM) control of the UPS inverter, to simplify the UPS control circuit, to improve the stability, to have more real-time UPS to quickly respond to changes in the external environment and guarantee the machine's control circuit is more simple and reliable.
2.Using digital control techniques, to avoid the traditional analog control temperature drift inherent defects such as hardware parameters, to ensure consistency and reliability of UPS.
- Parameter
Model | HW9116C PlUS 1-10KVA | ||||||||||
1KVA | 2KVA | 3KVA | 6KVA | 10KVA | |||||||
Capacity | 1KVA/0.7KW | 2KVA/1.4KW | 3KVA/2.1KW | 6KVA/4.2KW | 10KVA/7KW | ||||||
Nominal Voltage | 220/230/240VAC | ||||||||||
Nominal Frequency | 50Hz/60Hz | ||||||||||
Input | |||||||||||
Voltage Range | 115~295VAC(±3VAC) | 176~297VAC(±3VAC) | |||||||||
Frequency Range | 50HZ:(46Hz~54Hz); 60Hz:(56Hz~65Hz) | ||||||||||
Soft Start | 0~100% 5sec | ||||||||||
Power Factor | 0.98 | ||||||||||
Output | |||||||||||
Voltage Precision | 223/230/240x(1±2%) | ||||||||||
Frequency Precision | 50/60Hz±0.05Hz | ||||||||||
Power Factor | 0.8/0.9(Optional) Standard 0.8 | ||||||||||
Wave Distortion | Linear load<3% Non-linear<6% | ||||||||||
Overload Capability | Overload(110%~150%)for 30 seconds,then automatically transfer to bypass.when load is normal,it can automatically transfer to normal mode. | ||||||||||
Crest Factor | 3:1 | ||||||||||
Transfer Time | 0MS(AC to DC) | ||||||||||
Battery | |||||||||||
DC Supply Voltage | 36VDC | 96VDC | 96VDC | 240VDC | 240VDC | ||||||
Charge Current | 4A/8A(optional) | 4A/8A(optional) | 4A/8A(optional) | 4.2A | 4.2A | ||||||
Internal Battery Caoacity | (38/65/80/100AH)optional | ||||||||||
Panel Displsy | |||||||||||
LED | Load level/Battery level,Battry indicator,Unility Power,Bypass,Overload,Fault | ||||||||||
Communications | |||||||||||
Communicate Interface | RS232、SNMP Card(optional) | ||||||||||
Work Environment | |||||||||||
Temperature | -40° C~50° C | ||||||||||
Humidity | 0~95%(Non-condensing) | ||||||||||
Storage Temperature | -25° C~55° C | ||||||||||
Elevation | <1500m | ||||||||||
Physical Characterisstics | |||||||||||
Weight(KG) | N.W | 85 | 125 | 125 | 150 | 155 | |||||
Dimensions(WxDxH)mm | 613x640x954 | 650x753x1227 | 650x753x1227 | 940x940x1770 | 940x90x1770 |